EasyManua.ls Logo

Siemens SIMATIC PCS 7 - Page 70

Siemens SIMATIC PCS 7
99 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Service and maintenance of SIMATIC PDM
6.6 Replacing/removing field devices
Compendium Part D - Operation and Maintenance (V9.0)
70 Operating Manual, 02/2018, A5E43228948-AA
PA device (PDM V9.1) procedure
In this example, a Siemens SITRANS LR250 level radar is replaced with a Siemens
SITRANS LR260 level radar.
1. In HW Config, select "Object Properties" from the shortcut menu of the LR250.
2. Back up all project-specific information and settings from the "General" and "Assign
Parameters" tabs. You will need this information for configuring and assigning parameters
for the new device type.
3. Make a backup of the symbol table (E address).
4. Switch to the process device plant view to back up the LR250 parameter set.
SIMATIC PDM opens.
5. Select the device "LR250_Compend" and select "Export..." in the shortcut menu.
The export dialog is opened. Using the export dialog, you can back up the device
parameters and diagnostics and document manager information.

Table of Contents

Other manuals for Siemens SIMATIC PCS 7

Related product manuals