AS and OS expansions 
  7.1 Changes to the AS configuration 
Compendium Part D - Operation and Maintenance (V9.0) 
Operating Manual, 02/2018, A5E43228948-AA 
79 
Which parameters cannot be changed during operation of an H system (selection for typical 
PCS 7 projects)? 
●  CPU: Activation of process image partition 
●  CPU: Size of maximum local data requirements 
●  Setting for time synchronization 
●  Transmission rate to the DP master systems 
●  Settings on the Ethernet CP and PROFIBUS CP 
●  Changing the I/O addresses 
Checking the plant status 
The following requirements must be met prior to making the changes: 
●  The H system is in "Redundant" system mode. 
●  All redundant DP slaves are ready for the upcoming master/standby switchover; in other 
words, no redundancy errors are pending on the H system or other errors on the interface 
module. 
Note 
If a fault is pending on an interface module, the master/standby switchover will cause the 
system to indicate a station failure of the DP slave concern
ed when the configuration is 
As of PCS 7 V7.0 SP2, related problems with the signal modules concerned are resolved 
automatically as soon as the configuration change is active. 
With older PCS 7 versions, the ACC input must first be set o
n the MOD_D1 driver blocks 
concerned to ensure that these problems will be resolved.
●  All changes must be downloaded via HW Config using "Download station configuration in 
RUN mode". The "Compile and download objects" function in SIMATIC Manager cannot 
be used for this purpose.