Technical specifications
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
160 Manual, 12/2017, A5E40898741-AA
– Frequency measurement
100 ppm; depending on measuring interval and
– Cycle duration measurement
100 ppm; depending on measuring interval and
– Velocity measurement
100 ppm; depending on measuring interval and
Potential separation digital inputs
• between the channels
No
• between the channels, in groups of
16
Potential separation digital outputs
• between the channels
No
• between the channels, in groups of
16
Potential separation channels
• between the channels and backplane bus
Yes
• Between the channels and load voltage L+
No
Ambient temperature during operation
• horizontal installation, min.
0 °C
• horizontal installation, max.
60 °C; Note derating data for onboard I/O in the
manual. Display: 50 °C, at an operating tempera-
ture of typically 50 °C, the display is switched off
• vertical installation, min.
0 °C
• vertical installation, max.
40 °C; Note derating data for onboard I/O in the
manual. Display: 40 °C, at an operating tempera-
ture of typically 40 °C, the display is switched off
Ambient temperature during stor-
age/transportation
• min.
-40 °C
• max.
70 °C
– LAD
Yes
– FBD
Yes
– STL
Yes
– SCL
Yes
– GRAPH
Yes