EasyManua.ls Logo

Siemens Simatic S7-1500 CPU 1512C-1 PN - Page 48

Siemens Simatic S7-1500 CPU 1512C-1 PN
206 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technology functions
3.1 High-speed counters
CPU 1512C-1 PN (6ES7512-1CK01-0AB0)
48 Manual, 12/2017, A5E40898741-AA
Control interface per channel
The following table shows the control interface assignment:
Table 3- 3 Assignment of the control interface
Offset from start
address
Parameter
Meaning
Bytes 0 to 3
Slot 0
Load value (meaning of the value is specified in LD_SLOT_0)
Bytes 4 to 7 Slot 1 Load value (meaning of the value is specified in LD_SLOT_1)
Byte 8 LD_SLOT_0*
Specifies the meaning of the value in Slot 0
Bit 3
Bit 2
Bit 1
Bit 0
0
0
0
0
No action, idle state
0
0
0
1
Load counter
0
0
1
0
Reserve
0
0
1
1
Load start value
0
1
0
0
Load comparison value 0
0
1
0
1
Load comparison value 1
0
1
1
0
Load low counting limit
0
1
1
1
Load high counting limit
1
0
0
0
Reserve
to
1
1
1
1
LD_SLOT_1*
Specifies the meaning of the value in Slot 1
Bit 7
Bit 6
Bit 5
Bit 4
0
0
0
0
No action, idle state
0
0
0
1
Load counter
0
0
1
0
Reserve
0 0 1 1 Load start value
0
1
0
0
Load comparison value 0
0
1
0
1
Load comparison value 1
0
1
1
0
Load low counting limit
0
1
1
1
Load high counting limit
1
0
0
0
Reserve
to
1
1
1
1
Byte 9
EN_CAPTURE
Bit 7: Enable capture function
EN_SYNC_DN
Bit 6: Enable downward synchronization
EN_SYNC_UP
Bit 5: Enable upward synchronization
SET_DQ1
Bit 4: Set DQ1
SET_DQ0
Bit 3: Set DQ0
TM_CTRL_DQ1
Bit 2: Enable technological function DQ1
TM_CTRL_DQ0
Bit 1: Enable technological function DQ0
SW_GATE
Bit 0: Software gate

Table of Contents

Related product manuals