Basic Principles of Serial Data Transmission
2.8 Configuration data
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
104 Manual, 09/2008, A5E02191071-01
Examples of invalid conversion statements
Below are several examples of invalid conversion statements.
Example 1: ******.2R
Format string = %303.2R
Variable 1 = 1.2345E6
Error: Invalid width in the R display type. The maximum permissible value for all display
types is 255.
Example 2: ****
Format string = %4.1I
Variable 1 = 12345 DEC
Error: The selected width was too small for the variable value to be output. The precision is
not relevant to display type I.
Example 3: 96–10–3
Format string = %7.2D
Variable 1 = D#1996–10–31
Error: The format string is formally correct, but the selected width was too small to print the
date in full.
Example 4: **********
Format string = %.3A
Variable 1 = D#1996–10–31
Error: The default width of display type A was selected but with invalid precision. The
possible values here are 2 and 4.
Example 5: ******
Format string = %3.3
Variable 1 = 12345 HEX
Error: A display type was not specified.