Basic Principles of Serial Data Transmission
2.8 Configuration data
CP 341 Point-to-Point Communication, Installation and Parameter Assignment
92 Manual, 09/2008, A5E02191071-01
X27 (RS 422/485) interface
You will find a description of the parameters for the X27 (RS 422/485) interface in the table
below.
Table 2- 15 X27 (RS 422/485) interface (ASCII driver)
Parameters Description Range of values Default value
Operating mode Specifies whether the X27 (RS 422/485)
interface is to be operated in full-duplex
(RS 422) or half-duplex (RS 485) mode.
(See also Serial Transmission of a
Character (Page 29))
Full-duplex (RS 422)
four-wire mode
Half-duplex (RS 485)
two-wire mode
Full-duplex (RS 422)
four-wire mode
Receive line initial state None: This setting only makes sense with
bus-capable special drivers.
R(A) 5V / R(B) 0V: This default setting
supports break detection in "Full-duplex
(RS 422) four-wire mode".
R(A) 0V / R(B) 5V: This default
corresponds to idle state (no senders
active) in "Half-duplex (RS 485) two-wire
mode". Break detection is not possible in
this initial state.
(also see the following figure)
None
R(A) 5V / R(B) 0V
1
R(A) 0V / R(B) 5V
R(A) 5V / R(B) 0V
1
(In "Half-Duplex
(RS 485) Two-Wire
Mode", the default
setting is R(A) 0V /
R(B) 5V.)
Delete CP receive
buffer at startup
You can specify whether the CP receive
buffer should be deleted on startup or
existing (old) message frames should be
sent to the CPU.
Yes
No
No
1
Only in the case of "Full-Duplex (RS 422) Four-Wire Mode".