Status SF TXD RXD Comment Remedy
Firmware update in progress On On On - -
Firmware update completed On Off Off - -
CP 341 without module
firmware
Flashing
(2 Hz)
Off Off Module firmware
deleted, firmware update
canceled, firmware
update still possible
Reload the firmware
Hardware fault during firmware
update
Flashing
(2 Hz)
Flashing
(2 Hz)
Flashing
(2 Hz)
Delete/write operation
failed
Switch power supply to
module off and then on
again and reload the
firmware.
Check whether the
module is defective.