Expert Functions
5.2 Extending a PROFIdrive message frame
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
135
8. Switch to the "Details" tab and note the assignment of the PROFIBUS input/output
addresses. Each object of the configuration has its own area that is concluded with an
axis separator.
In this example, the selection of the two standard message frames starting at slot 10
creates the input/output area for the TB30 and the control unit.
9. Note for the subsequent steps the start addresses of the objects. In our example,
these are:
Object 3 - TB30 - Address 296
Object 4 - Control Unit - Address 300
10. Accept the suggested I/O addresses for both objects.
11. Click "OK" to close the configuration.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)