Safety Integrated Functions in
SINAMICS Drive Systems
6.5 Behavior and reactions in the user program
Connection of the SINAMICS S120 to the Technology CPU
Product Information, 09/2011, A5E00480378-04
201
Safely Limited Speed (SLS)
When SLS is selected, the drive continues to follow the setpoint interface and activates the
velocity monitoring after the delay time (p9351/p9551) configured in the drive.
Response in the user program
When SLS is selected (displayed in StatuswordSafety.SLS_Deselected=FALSE
(DBx 140.4)), the speed is reduced within the configured delay time to the maximum speed
defined by the TO DB variable, safeSpeedLimit.
When SLS is deselected, the drive deactivates the velocity monitoring. The drive can
traverse again without restriction provided no other safety function is active.
For selected SLS, the drive is in the monitored standstill (SOS or SS2)
The drive is in the monitored standstill (by a previous selection of SS2 or SOS).
A motion can then only be executed if SS2 and SOS are not active
(StatuswordSafety.SS2_Active=FALSE (DBx 140.2) and
StatuswordSafety.SOS_Selected=FALSE (DBx 140.3)).
Response in the user program:
When SS2 and SOS are deselected, a motion is permitted immediately with the
displayed maximum velocity safeSpeedLimit.
Axis performs motion
When SLS is selected, the axis traverses with a higher velocity than preselected
with SLS.
Response in the user program:
When SLS is selected (without stop function also active at the same time), the axis must
be reduced to the maximum velocity displayed as safeSpeedLimit within the configured
delay time.
Modification of velocity limitation
The velocity limit value monitored in the drive can be changed dynamically. A reduction of
the limit value is critical because the deceleration must be performed in the user program
to prevent violation of the new limit value.
Response in the user program:
If SLS is active (and all stop functions are inactive), the safeSpeedLimit system variable
will be monitored for change:
new safeSpeedLimit > old safeSpeedLimit: Higher velocity permitted immediately
new safeSpeedLimit > old safeSpeedLimit: Deceleration and limitation to the new limit
value within the configured delay time

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals