10.2.5 Explosion protection
ATEX approval DEKRA 21ATEX0010 X
Type examination certi󹪝cate number DEKRA 21ATEX0010 X
Standards EN IEC 60079-0
EN 60079-7
Marking II 3 G Ex ec IIC T4 Gc
The certi󹪝cate is valid for the "DEKRA 21ATEX0010 X" products listed in the certi󹪝cate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to
EN 60664‑1.
The modules must be installed in a suitable enclosure which provides a degree of protection
of at least IP54 in accordance with EN 60079‑7, taking into account the ambient conditions
of use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of
transient disturbance voltages.
IECEx approval IECEx DEK 21.0008X
Certi󹪝cate number IECEx DEK 21.0008X
Standards IEC 60079-0
IEC 60079-7
Marking Ex ec IIC T4 Gc
The certi󹪝cate is valid for the "IECEx DEK 21.0008X". products listed in the certi󹪝cate.
Special conditions
The device may only be used in areas with a pollution degree of no more than 2 according to
IEC 60664‑1.
The modules must be installed in a suitable enclosure which provides at least IP54 degree of
protection in accordance with IEC 60079‑7 and taking into account the ambient conditions
of use.
Measures must be taken to prevent exceeding the rated voltage by more than 119 V of
transient disturbance voltages.
Technical speci󹪝cations
10.2 Standards and approvals
Point-to-point connection CP 440 Installation and Parameter Assignment
Equipment Manual, 03/2022, A5E00057742-AE 123