EasyManua.ls Logo

Siemens Simatic S7-400

Siemens Simatic S7-400
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Time Sequence Chart for the RECV_440 FB
The 󹪝gure below illustrates the behavior of the NDR, LEN and ERROR parameters, depending on
how the EN_R and R inputs are wired.
1'5
(1B5
5
(5525
(QDEOHUHFHLYH
&RPSOHWLRQZLWKRXWHUURUV
5HFHLYLQJ
7HUPLQDWLRQZLWKHUURUV
5HFHLYLQJLVVZLWFKHGRII
1RWUHFHLYLQJ
5(6(7
&RPSOHWLRQZLWKRXWHUURUV
5HFHLYLQJ
7HUPLQDWLRQZLWKHUURUV
/(1
OHQJWK
Figure 6-2 Time Sequence Chart for the 9 RECV_440 FB
Note
The EN_R must be set to static "1". During the receive request, the EN_R parameter must be
supplied with RLO "1" (result of logic operation).
6.3.3 Deleting the Receive Bu󹪜er (11 "RES_RECV" FB)
The RES_RECV FB deletes the entire receive bu󹪜er of the CP 440. All the stored message frames
are discarded. A message frame coming in at the same time as the RES_RECV FB call is saved.
The FB is activated by a positive edge at the REQ input. The job can run over several calls
(program cycles).
The FB RES_RECV function block can be called in the cycle when the signal state at the R
parameter input is "1". This terminates deletion and sets the RES_RECV FB back to its initial state.
Communication via Function Blocks
6.3 Using the Function Blocks
Point-to-point connection CP 440 Installation and Parameter Assignment
82 Equipment Manual, 03/2022, A5E00057742-AE

Table of Contents

Other manuals for Siemens Simatic S7-400

Related product manuals