Protocol parameters
You can only set the protocol parameters if you have not set the default values in the protocol.
Table 5-11 Protocol Parameters (3964(R) Procedure)
Parameter Description Value Range Default Val‐
ue
Character delay
time
The character delay time de󹪝nes the permis‐
sible maximum interval between two in‐
coming characters in a message frame.
20 ms to 65530 ms in 10 ms increments
The shortest character delay time depends
on the baud rate:
220 ms
300 bps
600 bps
1200 bps
2400 to 15200 bps
60 ms
40 ms
30 ms
20 ms
Acknowledge‐
ment delay time
(ADT)
The acknowledgment delay time de󹪝nes the
maximum amount of time permitted for the
partner's acknowledgment to arrive during
connection setup (time between STX and
partner's DLE acknowledgment) or release
(time between DLE ETX and partner's DLE
acknowledgment).
20 ms to 65530 ms in 10 ms increments
The shortest acknowledgment delay time
(ADT) depends on the baud rate:
2000 ms
(550 ms
with 3964
without
block check)
300 bps
600 bps
1200 bps
2400 to 15200 bps
60 ms
40 ms
30 ms
20 ms
Connection at‐
tempts
This parameter de󹪝nes the maximum num‐
ber of attempts the CP 440 is allowed in or‐
der to establish a connection.
1 to 255 6
Transmission at‐
tempts
This parameter de󹪝nes the maximum num‐
ber of attempts to transfer a message frame
(including the 󹪝rst one) in the event of an
error.
1 to 255 6
Con󹪝guring and Parameter Assignment the CP 440
5.4 Con󹪝guration data
Point-to-point connection CP 440 Installation and Parameter Assignment
Equipment Manual, 03/2022, A5E00057742-AE 65