Technical Data
4.3 D4x5 power supply
D4x5
Manual, 05/2009
59
An error message is output if the backup function is defective. When the power is switched
ON, the clock then resumes at the time set at the factory.
If the SIMOTION D4x5 is reset to its factory setting, the clock is also reset to the "default
setting when delivered".
4.3 D4x5 power supply
External 24 V power supply
Power is supplied to the control unit by an external 24 V power supply (e.g., SITOP).
The tolerance range for the SIMOTION D4x5 is between DC 20.4 and 28.8 V.
Table 4- 13 Input voltage specification
Input voltage Typ. current consumption
1)
Maximum current
consumption
D425 and
D435
D445 D425 and
D435
D445
(D445-1)
D425 and
D435
D445
(D445-1)
Minimum input
voltage
20.4 V 20.4 V 0.7 A 2.35 A
(1.18 A)
9.8 A 10.6 A
(10.3 A)
Nominal Input
voltage
24 V 24 V 0.6 A 2.0 A
(1 A)
8.4 A 9.0 A
(8.8 A)
Maximum input
voltage
28.8 V 28.8 V 0.5 A 1.67 A
(0.84 A)
7.0 A 7.5 A
(7.3 A)
1)
With no load on inputs/outputs (no 24 V supply via DRIVE-CLiQ or PROFIBUS interface)
Note
A primary-side voltage dip lasting for 20 ms must not cause the voltage on the secondary
side (24 V) to fall below the minimum permissible input voltage for the Control Unit.
Additional references
Recommended power supply units and tables for calculating the current consumption for the
assembly with SINAMICS S120 modules can be found in the "Cabinet Construction and
EMC Booksize" chapter in the
SINAMICS S120 Booksize Power Units
Manual.