Spare parts/accessories
6.2 Fan/battery module
D4x5
Manual, 05/2009
69
Table 6- 1 Fan/battery module for SIMOTION D4x5
Properties SIMOTION D425 SIMOTION D435 SIMOTION D445 SIMOTION D445-1
Fan/
battery
module
Optional D435 with order no.
6AU1 435-0AA00-
0AA1: optional
-----------------------------
D435 with order no.
6AU1 435-0AA00-
0AA0:
with air intake
temperature of 43 °C
or above
Always required
(included in the
D445's scope of
delivery)
Always required
(double fan/
battery module
included in the D445-
1's scope of delivery)
Compatible
fan/
battery
modules
Fan/
battery module
(single fan)
Fan/battery module
(single fan)
Fan/battery
module (single
fan)
Double fan/
battery module
Fan/battery module
(single fan)
Max.
permissible
air intake
temperature
55 °C 55°C 55°C 55°C
Fan control Switches on at
air intake
temperatures of
approx. 43 °C or
above
switches on when air
intake temperature
exceeds approx. 43°C
The fan runs all
the time
Temperature-
controlled fan;
activated when
required and runs
constantly at air intake
temperatures of
approx. 40 °C or
above
The double fan/battery module also guarantees sufficient cooling with just one functional fan.
If one of the fans fails, the remaining fan continues under full load. The fan failure is signaled
by the generation of an event in the PeripheralFaultTask.
Fan faults are displayed and can be read out by means of the diagnostic buffer. The SF LED
illuminates red/yellow (2 Hz) in the event of temperature or fan faults.
NOTICE
The 80 mm clearances above and below the components must be observed. The unit
protects itself from overheating by shutting down.
The clearance below the component is calculated from the bottom edge of the module, i.e. if
there is a fan, it will not be included in the clearance.