01.04 Parameter list
SIEMENS AG 6SG7000-0BA76 11-51
SIMOTRAS HD Operating Instructions
PNU Description Value range
[Unit]
No. indices See
Change
11.33 Control word, status word
Selection of sources of control words 1 and 2
P648
*
BDS
(G180)
Source for control word 1
Selection of connector to act as the source for control word 1.
0 = connector K0000
...
8 = connector K0008
9 = parameters P654 to P675 are effective
(every individual bit of control word 1 is input by a binector)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 2
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
P649
*
BDS
(G181)
Source for control word 2
Selection of connector to act as the source for control word 2.
0 = connector K0000
...
8 = connector K0008
9 = parameters P676 to P691 are effective
(every individual bit of control word 2 is input by a binector)
10 = connector K0010
etc.
All connector
numbers
1
Ind: 2
FS=9
Type: L2
P052 = 3
P051 = 40
Offline
Display of control words 1 and 2
r650
(G180)
Display of control word 1
Representation on operator panel (PMU):
3210
4
5
6
7
89101112131415
Segments 0 to 15 correspond to bits 0 to 15 of the status word
Segment ON: Corresponding bit is in log. "1" state
Segment OFF: Corresponding bit is in log. "0" state
Ind: None
Type: V2
P052 = 3
r651
(G181)
Display of control word 2
Representation on operator panel (PMU):
3210
4
5
6
7
89101112131415
Segments 0 to 15 correspond to bits 16 to 31 of the status word
Segment ON: Corresponding bit is in log. "1" state
Segment OFF: Corresponding bit is in log. "0" state
Ind: None
Type: V2
P052 = 3
Display of status words 1 and 2
r652
(G182)
Display of status word 1
Representation on operator panel (PMU):
3210
4
5
6
7
89101112131415
Segments 0 to 15 correspond to bits 0 to 15 of the status word
Segment ON: Corresponding bit is in log. "1" state
Segment OFF: Corresponding bit is in log. "0" state
Ind: None
Type: V2
P052 = 3