Parameter list 01.04
11-150 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
PNU Description Value range
[Unit]
No. indices See
Change
11.83 Configuration of paralleling interface
Notes about parameterization of the paralleling interface see Chapter 6.3.2
U800
(2800)
*
(G195)
Control word for parallel connection of SIMOTRAS converters
[SW 2.1 and later]
0: SIMOTRAS converters are not connected in parallel
1: SIMOTRAS converters are connected in parallel
The gating pulses are generated by each individual converter
2: SIMOTRAS converters are connected in parallel
The gating pulses are generated by the master for all slaves
0 to 2
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Offline
U803
(2803)
*
(G195)
Operating mode for the parallel connection [SW 2.1 and later]
0 Standard mode
1 Do not set
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
off-line
U804
(2804)
*
(G195)
Transmit data on paralleling interface [SW 2.1 and later]
Selection of connectors whose contents must be injected as transmit data
(master to slaves or slave to master) for the paralleling interface.
0 = connector K0000
1 = connector K0001
etc.
This parameter not only defines the transmit data, but also their position in
the transmit telegram.
i001: Word 1 of telegram
...
i005: Word 5 of telegram
i006: Do not change the adjusting!
...
i010: Do not change the adjusting!
All connector
numbers
1
Ind: 10
FS=0
Type: L2
P052 = 3
P051 = 40
Online
U805
(2805)
(G195)
Control word for bus terminator of paralleling interface
[SW 2.1 and later]
0: No bus terminator
1: Bus terminator active
0 to 1
1
Ind: None
FS=0
Type: O2
P052 = 3
P051 = 40
Online
U806
(2806)
*
(G195)
Address for the parallel connection of SIMOTRAS devices
[SW 2.1 and later]
i001: Address of the masters or of the slaves
i002: Address of the masters or of the slaves
(i001 and i002 must be set to the same value)
2: Slave device with address 2
3: Slave device with address 3
4: Slave device with address 4
5: Slave device with address 5
6: Slave device with address 6
12: Master device for 1 slave device with address 2
13: Master device for 2 slave devices with addresses 2 and 3
14: Master device for 3 slave devices with addresses 2, 3 and 4
15: Master device for 4 slave devices with addresses 2, 3, 4 and 5
16: Master device for 5 slave devices with addresses 2, 3, 4, 5 and
6
see column on left Ind: 2
FS=2
Type: O2
P052 = 3
P051 = 40
off-line