01.04 Parameter list
SIEMENS AG 6SG7000-0BA76 11-151
SIMOTRAS HD Operating Instructions
PNU Description Value range
[Unit]
No. indices See
Change
U807
(2807)
(G195)
Telegram failure time on paralleling interface [SW 2.1 and later]
0 No time monitoring
0.001...65.000 Permissible time interval between two data exchange
operations before a fault message is output.
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period.
The monitoring function is implemented within a 20 ms cycle. For this
reason, only setting values which constitute a multiple of 20 ms are
meaningful.
Note:
The telegram monitoring function is active
from the receipt of the first error-free telegram after connection of the
electronics power supply
from the receipt of the first error-free telegram after the telegram
monitor has responded (i.e. monitoring timeout).
0.000 to 65.000
[s]
0.001s
Ind: None
FS=0.100
Type: O2
P052 = 3
P051 = 40
Online
U808
(2808)
*
(G195)
Source for triggering of message F014 [SW 2.1 and later]
Selection of binector which must trigger message F014 when it switches to
log. "1"
6040 = binector B6040
6041 = binector B6041
6040, 6041 Ind: None
FS=6040
Type: L2
P052 = 3
P051 = 40
Offline
n809
(2809)
(G195)
Diagnostic information for paralleling interface [SW 2.1 and later]
i001 to i009 = Free-running counter, overflow at 65535
i001: Number of error-free telegrams
i002: Number of errored telegrams
i003: Transmit Error Counter
i004: Receive Error Counter
i005: Phase Error Counter
i006: Baud rate Error Counter
i007: Bad BCC Counter
i008: Timeout Counter
i009: Number of telegrams with unknown identifier
0 to 65535 Ind: 9
Type: O2
P052 0