Connectors and binectors 01.04
12-26 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Binector Name, description Function
diag., Sheet
B0149
Stat.word 2, bit 24 inverted
G183
B0150
Stat.word 2, bit 25: 0=no motor overtemperature alarm active, 1=motor overtemperature alarm active
G183
B0151
Stat.word 2, bit 25 inverted
G183
B0152
Stat.word 2, bit 26: 0=no motor overtemperature fault active, 1=motor overtemperature fault active
G183
B0153
Stat.word 2, bit 26 inverted
G183
B0156
Stat.word 2, bit 28: 0=no motor blocked fault active, 1=motor blocked fault active
G183
Messages
B0160
0=AUS1 or AUS3 active, 1=no AUS1 and no AUS3 is pending
G180
B0161
B0160 inverted
G180
B0164
1 = n < n
min
G188
B0165
B0164 inverted
G188
B0166
1 = Voltage at power section is active
B0167
B0166 inverted
B0170
1=Voltage at power section AND operating state <= o7
G119
B0171
B0170 inverted
G119
B0172
Output of "Setpoint-actual value deviation 2" signal [SW 1.9 and later] G187
B0173
B0172 inverted [SW 1.9 and later] G187
Acknowledgement of fault codes [SW 2.1 and later]
B0179
Acknowledgement of control word or P key on PMU (pulse) G180
Binary inputs
B0180
1=Terminal 211 not activated for more than 10 s.
G186
B0181
1=Terminal 212 activated for more than 2 s.
G186
B0182
1=Terminal 213 not activated for more than 40 s while in operating state < o6
G186
B0183
1=Terminal 214 not activated for more than 10 s.
G186
Temperature sensor inputs
B0184
1=Alarm motor temperature 1
G185
B0185
1=Alarm motor temperature 2
G185
Alarm messages
B0186
1=Alarm A037 (I2t motor) active
B0187
1=Alarm A039 (I2t power section) active
B0188
1=Alarm A067 (heatsink temperature) active
B0189
1=Alarm A067 (converter fan) active
Torque limitation, current limitation, current controller
B0190
0 = pulsating current, 1 = continuous current [SW 2.0 and later] G162
B0192
Speed limitation controller: Positive speed limit reached [SW 1.8 and later] G160
B0193
Speed limitation controller: Negative speed limit reached [SW 1.8 and later] G160
B0194
Current limitation: Positive current limit reached [SW 1.8 and later] G161
B0195
Current limitation: Negative current limit reached [SW 1.8 and later] G161
B0198
Any positive limit (speed, torque, current) reached [SW 2.0 and later]
B0199
Any positive limit (speed, torque, current) reached [SW 2.0 and later]
B0200
Current limitation active G161
B0201
Speed limiting controller active G160
B0202
Upper torque limitation active G160