18-2 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Term. 81/82 (MB .. ready message) U621.001 = 162 [G119.3]
U621.002 = 162 [G119.3]
Term. 83/84 (ST .. setpoint in controlled
range)
U622.001 = 540 [G119.3]
U622.002 = 540 [G119.3]
Term. 85/86 (BR .. n n_min)
U623.001 = 165 [G119.3]
U623.002 = 165 [G119.3]
Term. 87/88 (S1 .. rotor contactor stage 1) [G119.4]
Term. 89/92 (S2 .. rotor contactor stage 2) For SIMOTRAS HD this is Term. 89/90 [G119.4]
Term. 90/92 (S3 .. rotor contactor stage 3) For SIMOTRAS HD this is Term. 91/92 [G119.4]
Term. 91/92 (S4 .. rotor contactor stage 4) For SIMOTRAS HD this is Term. 93/94 [G119.4]
Terminals 90, 92 and 94 must be linked
Term. 11/22 (MW .. message “temperature
pre-warning”)
For SIMOTRAS HD this is Term. 109/110 [G112.6]
U619.001 = 148 [G112.3]
U619.002 = 148 [G112.3]
Potentiometer on SIMOTRAS HE
(6GA4625 series)
Corresponding parameter on SIMOTRAS HD
(6SG70 series)
TF – Delayed enable P319 (factory setting = 0.05 s) [G136.2]
TZ – Brake application time monitoring This function must be implemented using free
modules if required (similar to ramp-down
monitoring on Sheet K15 in Section 8)
NT – Tachometer voltage normalization P741 (factory setting = 60.00 V) [G113.2]
NS – Speed setpoint normalization P320 (factory setting = 100.00 %) [G135.2]
SH – Lift start pulse U651 (factory setting = 0.00 %) [G150.2]
NZ – Additional setpoint normalization No setting necessary as the “zero delay angle”
function is implemented in a different way.
HR – Clockwise acceleration ramp P303 (factory setting = 10.00 s) *) [G136.2]
AR – Clockwise deceleration ramp P304 (factory setting = 10.00 s) *) [G136.3]
HL – Anticlockwise acceleration ramp P303 (factory setting = 10.00 s) *) [G136.2]
AL – Anticlockwise deceleration ramp P304 (factory setting = 10.00 s) *) [G136.3]
VR – n controller gain P225 (factory setting = 3.00) [G151.2]
ND – Speed monitoring normalization P388 (factory setting = 5.00 %) [G187.5]
ST – Setpoint in controlled range U628 (factory setting = 55.0 %) [G160.6]
BR – Standstill monitoring P370 (factory setting = 5.00 %) [G188.4]
S1 – Switching logic rotor contactor stage 1 U630 (factory setting = - 1.0 %) [G119.2]
S2 – Switching logic rotor contactor stage 2 U634 (factory setting = 50.0 %) [G119.6]
S3 – Switching logic rotor contactor stage 3 U636 (factory setting = 75.0 %) [G119.6]
S4 – Switching logic rotor contactor stage 4 U638 (factory setting = 90.0 %) [G119.6]
*) If the ramp-up and ramp-down functions for clockwise and anti-clockwise rotation are to be set
separately, the function data set must be switched over.