01.04 Connections
SIEMENS AG 6SG7000-0BA76 6-35
SIMOTRAS HD Operating Instructions
Temperature sensor inputs
(see also Section 8, Sheet G185)
Function Terminal
X174
Connection values/Remarks
Motor temperature
Connection of temperature sensor
22
23
Sensor acc. to P490 index 1
The cable to the temperature sensor on the motor must
be shielded and connected to ground at both ends.
Ground analog M 24
Analog outputs (see also Section 8, Sheet G115)
Function Terminal
X175
Connection values/Remarks
Actual current
Ground analog M
12
13
0. . .±10V corresponds to 0. . .±200%
Converter rated current
Max. load 2mA, short-circuit-proof
Select output analog 1
Ground analog M
14
15
Select output analog 2
Ground analog M
16
17
0
. . . ±10V, max. 2mA
short-circuit proof
Resolution ±11bit
Binary inputs
(see also Section 8, Sheet G110)
Function Terminal
X171
Connection values/Remarks
Supply for binary inputs
(output)
34 24V DC, short circuit proof
max. load 200mA (terminals 34, 44, and 210 combined),
internal supply with respect to internal ground
Ground digital M 35 Overload response: Error signal F018
Warning signal A018
Select input binary 1 36
Power On / Shutdown
1 = power on
0 = shutdown
37
Enable operation
1 = enable controller
0 = disable controller
38
Select input binary 2 39
H signal: +13V to +33V
L signal: – 33V to +3V or terminal open
8.5mA at 24V
Binary outputs
(see also Section 8, Sheet G112)
Function Terminal
X171
Connection values/Remarks
Select output binary 1
Ground M
46
47
Select output binary 2
Ground M
48
54
H signal: +20V to +26V
L signal: 0 to +2V
Short-circuit-proof 100mA
Internal snubber circuit (free-wheeling diode)
Overload response: Error signal F018
Warning signal A018