Connections 01.04
6-40 SIEMENS AG 6SG7000-0BA76
SIMOTRAS HD Operating Instructions
Analog inputs
(see also Section 8, Sheet G114)
Function Terminal
X164
Connection values/Remarks
Select input analog 2
Ground analog
8
9
Select input analog 3
Ground analog
10
11
±10V, 52k
Ω
Resolution: ±10bit
Common mode suppression: ±15V
Analog outputs, temperature sensor input
(see also Section 8, Sheets G116 and G185)
Function Terminal
X164
Connection values/Remarks
Select output analog 3
Ground analog M
18
19
Select output analog 4
Ground analog M
20
21
0
. . . ±10V, max. 2mA
short-circuit proof
Resolution ±11bit
Temperature sensor input
204
205
Sensor acc. to P490 Index 2
The cable to the temperature sensor on the motor must
be shielded and connected to ground at both ends.
Serial interface 3 (G-SST3) RS485
Function Terminal
X162
Connection values/Remarks
TX+ 61 RS485, 4-wire send cable, positive differential input
TX- 62 RS485, 4-wire send cable, negative differential input
RX+/TX+ 63 RS485, 4-wire receive cable, positive differential input,
2-wire send/receive cable, positive differential input
RX-/TX- 64 RS485, 4-wire receive cable, negative differential input,
2-wire send/receive cable, negative differential input
M 65 Ground
Cable length: For transmission rate =187.5kBd
⇒ 600m
For transmission rate
=93.75kBd ⇒ 1200m
The following must be observed: DIN 19245 Part 1
The potential difference between the data reference potentials M of all interfaces must not
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be
provided.
Activate interface 3:
– Set the baud rate in parameter P803.
– Set the protocol in parameter P800.