01.04 Connections
SIEMENS AG 6SG7000-0BA76 6-39
SIMOTRAS HD Operating Instructions
Options:
Terminal expansion (C98043-A7006)
Terminal type
: Plug-in terminal (screw-type)
Max. connection cross-section 1.5mm
2
Binary inputs, fault and alarm messages
(see also Section 8, Sheet G186)
Function Terminal
X161
Connection values/Remarks
Supply for binary inputs
(output)
210 24V DC, short circuit proof with respect to internal ground
max. load 200mA (terminals 34, 44, and 210 combined),
Overload response: Error signal F018
Warning signal A018
Binary input
Binary input
Binary input
Binary input
211
212
213
214
H signal: +13V to +33V
L signal: – 33V to +3V or terminal open
Input resistance = 2.8 k
Ground for binary inputs
Ground for binary inputs
M
215
216
217
can be isolated from internal ground
(open wire jumper between terminals 216 and 217)
Binary inputs
(see also Section 8, Sheet G111)
Function Terminal
X163
Connection values/Remarks
Supply for binary inputs
(output)
44 24V DC, short circuit proof
max. load 200mA (terminals 34, 44, and 210 combined),
internal supply with respect to internal ground
Ground digital M 45 Overload response: Error signal F018
Warning signal A018
Select input binary 2 40
Select input binary 3 41
Select input binary 4 42
Select input binary 5 43
H signal: +13V to +33V
L signal: – 33V to +3V or terminal open
8.5mA at 24V
Binary outputs
(see also Section 8, Sheet G112)
Function Terminal
X163
Connection values/Remarks
Select output binary 3 50
Ground M 51
Select output binary 4 52
Ground M 53
H signal: +20V to +26V
L signal: 0 to +2V
Short-circuit-proof 100mA
Overload response: Error signal F018
Warning signal A018
Internal snubber circuit (free-wheeling diode)