Functions
5.11 Operation in fieldbus systems
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
155
The meaning of the response ID for response message frames (converter → master) is
explained in the following table. The request ID determines which response IDs are possible.
Table 5- 53 Response ID (converter → master)
Response ID Description
0 No response
1 Transferred parameter value (word)
2 Transferred parameter value (double word)
3 Transfer descriptive element
1)
4 Transfer parameter value (field, word)
2)
5 Transfer parameter value (field, double word)
2)
6 Transfer no. of field elements
7 The request cannot be processed and the task cannot be executed (with fault
number)
8 No master controller mode / no authorization to change parameters of the
PARAMETER CHANNEL interface
1) The required element of the parameter description is specified in IND (second word).
2) The required element of the indexed parameter is specified in IND (second word).