Functions
5.11 Operation in fieldbus systems
Frequency inverter
154 Operating Instructions, 08.10. 2008, t.b.d.
Table 5- 51 Sample coding of a parameter number in PKE and IND for P8820, index 16
PKE IND
decimal xx 820 32 16
hex xx 334 20 10
The parameter index is encoded in the second word of the index (IND).
Example: Coding of a parameter number in PKE and IND for P2016, index 3
3.(
[[

,1' 3:( 3:(
The master and slave exchange data via the request ID and response ID (AK), a process
that is to take place with the parameter specified in the PKE. The transfer status is
communicated with the response ID.
Table 5- 52 Request ID (master → converter)
Response
ID
Request
ID
Description
positive negative
0 No request 0 7 / 8
1 Request parameter value 1 / 2 7 / 8
2 Change parameter value (word) 1 7 / 8
3 Change parameter value (double word) 2 7 / 8
4 Request descriptive element
1)
3 7 / 8
6 Request parameter value (field)
1)
4 / 5 7 / 8
7 Change parameter value (field, word)
1)
4 7 / 8
8 Change parameter value (field, double word)
1)
5 7 / 8
9 Request no. of field elements 6 7 / 8
11 Change parameter value (field, double word) and save in EEPROM
2)
5 7 / 8
12 Change parameter value (field, word) and save in EEPROM
2)
4 7 / 8
13 Change parameter value (double word) and save in EEPROM 2 7 / 8
14 Change parameter value (word) and save in EEPROM 1 7 / 8
1) The required element of the parameter description is specified in IND (second word).
2) The required element of the indexed parameter is specified in IND (second word).