Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
156 Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
AI1 ANALOG IN 1 AI1 input signal V/mA inverter-dependent R r0752[1]
AI3 ANALOG IN 3 AI3 input signal V/mA inverter-dependent R r0752[3]
AV9 MOTOR TEMP Measured or calculated motor
°C inverter-dependent R r0035
AV10 KWH NR Cumulative inverter energy
consumption (cannot be reset!)
kWh inverter-dependent R r0039
AV12 INV RUN TIME Motor's operating hours (is reset
h 0 … 4294967295 W p0650
Code number of Power Module
Rated power of the inverter
AV16 SPEED
Reference speed of the inverter RPM 6.0 … 210000 W p2000