Communication via RS485
5.5 Communication via BACnet MS/TP - only CU230P-2 HVAC / BT
Fieldbuses
Function Manual, 04/2018, FW V4.7 SP10, A5E34229197B AE
157
AV17 FREQ SP PCT Setpoint 1 (when controlling via
% -199.99 … 199.99 C HSW
AV18 ACT FAULT Number of the fault due to be
dealt with
--- inverter-dependent R r0947[0]
Number of the fault before last
AV21 PREV FAULT 3 Number of the fault third from
--- inverter-dependent R r0947[3]
AV22 PREV FAULT 4 Number of the fault fourth from
--- inverter-dependent R r0947[4]
AV25 SEL STPT Command to select the setpoint
--- 0 … 32767 W p1000
AV31 MAX Speed Maximum speed RPM 0.000 … 210000.00
W p1082
AV39 ACT WARN Indication of a pending alarm --- inverter-dependent R r2110[0]
Indication of the last alarm
AV41 PREV WARN 2 Indication of the last but one
alarm
--- inverter-dependent R r2110[2]
AV5000 RAMP UP TIME Technology controller ramp-up
s 0 … 650 W p2257
AV5001 RAMP DOWN TIME Technology controller ramp-
s 0 … 650 W p2258
AV5002 FILTER TIME Technology controller actual
value filter time constant
s 0 … 60 W p2265
AV5003 DIFF TIME Technology controller differenti-
s 0 … 60 W p2274
AV5004 PROP GAIN Technology controller propor-
s 0 … 1000 W p2280
AV5005 INTEG TIME Technology controller integral
s 0 … 1000 W p2285
AV5006 OUTPUT MAX Technology controller maximum
% - 200 … 200 W p2291
AV5007 OUTPUT MIN Technology controller minimum
% - 200 … 200 W p2292
AV5100 RAMP UP TIME 0 Technology controller 0 ramp-up
s 0 … 650 W p11057
AV5101 RAMP DOWN TIME 0 Technology controller 0 ramp-
s 0 … 650 W p11058
AV5102 FILTER TIME 0 Technology controller 0 actual
value filter time constant
s 0 … 60 W p11065