Technical data
6.6 690 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
103
Table 6- 34 PM240-2, IP20, frame size F, 500 V … 690 V 3 AC
Article No. - without filter
Article No. - with filter
6SL3210-1PH28-0UL0
6SL3210-1PH28-0AL0
6SL3210-1PH31-0UL0
6SL3210-1PH31-0AL0
6SL3210-1PH31-2UL0
6SL3210-1PH31-2AL0
LO base load power 75 kW 90 kW 110 kW
LO base load input current 78 A 97 A 111 A
LO base load output current 80 A 100 A 115 A
HO base load power
55 kW
75 kW
90 kW
HO base load input current
66 A
85 A
106 A
HO base load output current 62 A 80 A 100 A
Siemens fuse according to IEC
Fuse according to UL, class J
3NA3830-6 (100 A)
100 A
3NA3132-6 (125 A)
125 A
3NA3136-6 (160 A)
150 A
Power loss without filter
1.37 kW
1.74 kW
1.95 kW
Power loss with filter
1.38 kW
1.76 kW
1.97 kW
Required cooling air flow
153 l/s
153 l/s
153 l/s
Weight without filter
61 kg
61 kg
61 kg
Weight with filter
65 kg
65 kg
65 kg
Table 6- 35 PM240-2, IP20, frame size F, 500 V … 690 V 3 AC
Article No. - without filter
Article No. - with filter
6SL3210-1PH31-4UL0
6SL3210-1PH31-4AL0
LO base load power
132 kW
LO base load input current
137 A
LO base load output current
142 A
HO base load power
110 kW
HO base load input current
122 A
HO base load output current 115 A
Siemens fuse according to IEC
Fuse according to UL, class J
3NA3140-6 (200 A)
200 A
Power loss without filter
2.48 kW
Power loss with filter 2.51 kW
Required cooling air flow 153 l/s
Weight without filter
61 kg
Weight with filter
65 kg