Connecting
4.2 Connecting the line and motor cable at the converter
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
57
Table 4- 3 Permissible cable lengths for the motor connection, FSF
with or without filter, with or
without output reactor
without filter, with two output
reactors in series
400 V 150 m 300 m 450 m 525 m 800 m
1)
Restriction for PT devices with 400
V: Use a double-shielded cable for the motor connection.
Table 4- 4 Permissible cable lengths for the motor connection, FSG
with or without filter, with or
without output reactor
without filter, with two output
reactors in series
400 V 150 m
1)
300 m 450 m 525 m 800 m
1)
4.2.3 Connection terminals at the converter
Table 4- 5 Connection, cross-section and tightening torque for PM240-2 Power Modules
Cross-section and tightening torque
Stripped
insulation
length
Line system, motor
and braking resistor
Plug connector
with screw termi-
2
2
6 …16 mm², 1.3 Nm 10 … 6 AWG, 12 lbf in 10 mm
Line and motor Screw-type termi-
nal
10 … 35 mm
2
,
8 … 2 AWG,
18 mm
Braking resistor 2.5 … 16 mm
2
,
20 … 6 AWG,
10 mm
Line and motor Screw-type termi-
nal
25 … 70 mm
2
,
6 … 3/0 AWG,
25 mm
Braking resistor 10 … 35 mm
2
,
2.5 … 4.5 Nm
8 … 2 AWG,
22 … 40 lbf in
18 mm