Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
25
3.2.2 Cables
Cables with a high level of interference and cables with a low level of interference are
connected to the converter:
Cables with a high level of interference:
Cable between the line filter and converter
Motor cable
Cable at the converter DC link connection
Cable between the converter and braking resistor
Cables with a low level of interference:
Cable between the line and line filter
Signal and data cables
Cable routing inside the cabinet
Route the power cables with a high level of interference so that there is a minimum
clearance of 25 cm to cables with a low level of interference.
If the minimum clearance of 25 cm is not possible, insert separating metal sheets
between the cables with a high level of interference and cables with a low level of
interference. Connect these separating metal sheets to the mounting plate to establish a
good electrical connection.
Cables with a high level of interference and cables with a low level of interference may
only cross over at right angles:
Keep all of the cables as short as possible.
Route all of the cables close to the mounting plates or cabinet frames.
Route signal and data cables - as well as the associated equipotential bonding cables -
parallel and close to one another.
Twist incoming and outgoing unshielded individual conductors.
Alternatively, you can route incoming and outgoing conductors in parallel, but close to
one another.
Ground any unused conductors of signal and data cables at both ends.
Signal and data cables must only enter the cabinet from one side, e.g. from below.
Use shielded cables for the following connections:
Cable between the converter and line filter
Cable between the converter and output reactor or sine-wave filter