Technical data
6.1 Electromagnetic compatibility - Overview
Power Module PM240-2
74 Hardware Installation Manual, 01/2020, A5E33294624B AL
6.1 Electromagnetic compatibility - Overview
Electromagnetic compatibility according to EN61800-3
Interference immunity The converters are suitable for use in the first and second industrial environments
Interference emission -
second environment
Category C2 for converters with integrated radio interference suppression filter
Category C2 for converters without filter with optional external radio interference suppres-
sion filter for grounded line supplies (recommended for operation in conjunc-
tion with a residual current protective device RCD)
Category C3 for 690-V converters with integrated radio interference suppression filter,
Category C4 for converters without integrated radio interference suppression filter for op-
eration on IT line supplies
Additional information as well as conditions for using the converter in the first environment
are provided in the following Section:
Electromagnetic compatibility of variable-speed drives (Page 107).