EasyManua.ls Logo

Siemens SINAMICS PM240-2 - Electromagnetic Compatibility - Overview

Siemens SINAMICS PM240-2
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.1 Electromagnetic compatibility - Overview
Power Module PM240-2
74 Hardware Installation Manual, 01/2020, A5E33294624B AL
6.1 Electromagnetic compatibility - Overview
Electromagnetic compatibility according to EN61800-3
Property
Version
Interference immunity The converters are suitable for use in the first and second industrial environments
Interference emission -
second environment
Category C2 for converters with integrated radio interference suppression filter
Category C2 for converters without filter with optional external radio interference suppres-
sion filter for grounded line supplies (recommended for operation in conjunc-
tion with a residual current protective device RCD)
Category C3 for 690-V converters with integrated radio interference suppression filter,
frame size FSF, FSG
Category C4 for converters without integrated radio interference suppression filter for op-
eration on IT line supplies
Additional information as well as conditions for using the converter in the first environment
are provided in the following Section:
Electromagnetic compatibility of variable-speed drives (Page 107).