Technical data
6.4 200 V converters
Power Module PM240-2
86 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 14 PM240-2, PT, frame size F, 200 V to 240 V 3 AC
Article No. without filter
LO base load power 55 kW
LO base load input current 172 A
LO base load output current
HO base load input current 164 A
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
3NA3142 (224 A)
1)
Required cooling air flow
1)
approx. 1.9 kW through the heatsink
6.4.3 Current derating depending on the pulse frequency, 200 V converters
LO base load output current [A]
6SL3210-1PC24-2UL0 11 42
35.7 29.4 25.2 21 18.9 16.8
6SL321 . -1PC26-8UL0 18.5 68
57.8 47.6 40.8 34 30.6 27.2
The permissible motor cable length depends on the particular cable type and the pulse frequency that
has been selected.