4.2 Connecting the line and motor cable at the converter
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
53
4.2 Connecting the line and motor cable at the converter
4.2.1 Connection overview
Note
Line reactor
No line reactor is required for FSD
FSG Power Modules.
Line filter
The converters are available with or without integrated line filter (Class A). For frame sizes
FSA
FSC, 3 AC 400 V, there are external filters (Class B regarding conducted emissions)
for increased EMC requirements.
Line filters (Page 125)
Line harmonics filter
If you use a lin
e harmonics filter you do not need a line reactor or a line filter.
Line harmonics filters (Page 126)
Output reactor
For frame sizes FSD
FSG no output reactor is required in many cases on account of the
long
cable lengths between the converter and the motor.
Output reactors (Page 144)
Braking resistor
Connect
a braking resistor to the converter via the R1 and R2 terminals.
Braking resistors (Page 133)
Figure 4-3 Block diagram of the converter, FSA ... FSC