Installing
3.2 EMC-compliant installation of a machine or system
Power Module PM240-2
26 Hardware Installation Manual, 01/2020, A5E33294624B AL
Figure 3-3 Routing converter cables inside and outside a control cabinet
Routing cables outside the control cabinet
● Maintain a minimum clearance of 25 cm between cables with a high level of interference
and cables with a low level of interference.
● Use shielded cables for the following connections:
– Converter motor cable
– Cable between the converter and braking resistor
– Signal and data cables
● Connect the motor cable shield to the motor enclosure using a PG gland that establishes
a good electrical connection.