Accessories
8.6 Line harmonics filter
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
127
Assignment tables
Power Module, 400 V
Line harmonics filter
Frame
size
Article number
Power [kW]
Article number
FSB 6SL3210-1PE21-4 . L0
6SL321 . -1PE21-8 . L0
5.5
7.5
UAC:FN34406112E2XXJRX
UAC:FN34408112E2XXJRX
FSC 6SL3210-1PE22-7 . L0
6SL321 . -1PE23-3 . L0
11
15
UAC:FN344011113E2FAJRX
UAC:FN344015113E2FAJRX
FSD 6SL3210-1PE23-8 . L0
6SL3210-1PE24-5 . L0
6SL3210-1PE26-0 . L0
6SL321 . -1PE27-5 . L0
18.5
22
30
37
UAC:FN344019113E2FAJRX
UAC:FN344022115E2FAJRX
UAC:FN344030115E2FAJRX
UAC:FN344037115E2FAJRX
FSE 6SL3210-1PE28-8 . L0
6SL321 . -1PE31-1 . L0
45
55
UAC:FN344045115E2FAJRX
UAC:FN344055115E2FAJRX
FSF 6SL3210-1PE31-5 . L0
6SL3210-1PE31-8 . L0
6SL3210-1PE32-1 . L0
6SL321 . -1PE32-5 . L0
75
90
110
132
UAC:FN344075116E2FAJRX
UAC:FN344090116E2FAJRX
UAC:FN3440110118E2FAJRX
UAC:FN3440132118E2FAJXX
FSG 6SL3210-1PE33-0 . L0
6SL3210-1PE33-7 . L0
6SL3210-1PE34-8 . L0
160
200
250
UAC:FN3440160118E2FAJXX
UAC:FN3440200118E2FAJXX
UAC:FN3440132118E2FAJXX
*)
*)
Two 132 kW filters in parallel are required.
If the expected input power exceeds the rating of the largest available filter, and a custom
solution is not desired, then two or more filters can be wired in parallel. In this mode of
operation, it is recommended to use filters with equal power ratings to ensure proper current
sharing.
NOTICE
Line harmonic filters for Power Modules with 160 kW, 200 kW and 250 kW
The following combinations must not be used with u/f control.
Power Module 160 kW with LHF: UAC:FN3440160118E2FAJXX
Power Module 200 kW with LHF: UAC:FN3440200118E2FAJXX
Power Module 250 kW with 2 LHF in parallel: UAC:FN3440132118E2FAJXX
When you use one of this combinations only the following settings of p1300 are allowed:
P1300 = 20,
P1300 = 21
P1300 = 22
P1300 = 23