EasyManua.ls Logo

Siemens SINAMICS PM240-2 - Page 34

Siemens SINAMICS PM240-2
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installing
3.4 Mounting the Power Modules
Power Module PM240-2
32 Hardware Installation Manual, 01/2020, A5E33294624B AL
Frame sizes FSDFSG
Table 3- 3 Dimensions depend on the Control Unit (CU) and HMI device [mm]
Frame
size
Width
[mm]
Height [mm]
Depth [mm]
without
shield
plate
with
shield
plate
without
CU
with
CU230P-2
1)
with
CU240B-2
1)
/
CU240E-2
1)
with
CU250S-2
1)
FSD
200
472
624
237
253
237
256
FSE
275
551
728
237
253
237
256
FSF
305
709
966
357
373
357
376
FSG
305
1000
1257
357
373
357
376
1)
With a Smart Access Module plus 9 mm
With blanking cover or with Operator Panel plus 11 mm.
Table 3- 4 Drilling dimensions, cooling clearances and fixing
Frame
size
Drilling dimensions [mm]
Cooling air clearances [mm]
1)
Fixing/torque [Nm]
h
b
c
Top
2)
Bottom
2)
Front
FSD
430
170
7
300
350
100
4 x M5 / 6.0
FSE
509
230
8.5
300
350
100
4 x M6 / 10
FSF
680
270
13
300
350
100
4 x M8 / 25
FSG
970.5
265
15
300
350
100
4 x M10 / 50
1)
The Power Module is designed for mounting without any lateral cooling air clearance. For toler-
ance reasons, we recommend a lateral clearance of approx. 1 mm.
2)
The top and bottom cooling air clearances refer to the Power Module without shield plate

Table of Contents

Other manuals for Siemens SINAMICS PM240-2

Related product manuals