Connecting 
   
Power Module PM240-2 
Hardware Installation Manual, 01/2020, A5E33294624B AL 
45 
●  For converters with rated input currents > 160 A referred to LO, use a Siemens modular 
RCCB device (MRCD type B 5SV8111-4KK) with a current transformer (5SV870.-2K), a 
circuit breaker (series 3VA1) and a trip element (3VA9988-0BL30). 
 
Figure 4-1  MRCD 
●  A dedicated RCD is used for every converter. 
●  The motor cables are shorter than 50 m (164 ft) shielded, or 100 m (328 ft) unshielded. 
Additional information about motor cables: 
Length of the motor cable (Page 56) 
Further protection and monitoring equipment 
(https://support.industry.siemens.com/cs/ww/en/view/109486009)