6.5.6 Connect the auxiliary voltage
Connect the auxiliary voltage 1-phase 230 VAC / 50 Hz
Connect the auxiliary voltage for, e.g. SITOP, GSV, closed-loop control, open-loop control, to
the terminal strip . The maximum permissible conductor cross-section is 4 mm
2
.
With options C30 - C49, the auxiliary voltage can be drawn from the matching transformer.
You will find notes in the circuit manual of the drive.
Connect the auxiliary voltage 3-phase 400 VAC / 50 Hz
1. Connect the auxiliary voltage for fans, precharging, etc. to the terminal box . The
maximum permissible conductor cross-section is 50 mm
2
.
2. To connect the cables, move the cover upward.
3. Attach the cables to the appropriate connections.
For detailed information, see "Terminal strips" and the circuit manual of the drive.
See also
Terminal assignments (Page 201)
Auxiliary voltage terminal 1-phase AC
Auxiliary voltage terminal 3-phase AC
Figure 6-7 Example: Connection for auxiliary voltages
Electrical connection
6.5 Connection
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017 117