Removing the cooling water
1. Place the catchment tray under the pipe union.
2. Close the inlet non-return valve and the outlet non-return valve . Unscrew the water
supply and outlet pipes .
Figure 9-11 Water connection
3. Capture the cooling water (approximately 5 liters) using the catchment tank. Remove all
water from the phase module.
Removing cables and screwed connections
1. Pull out the fiber-optic conductors.
2. Remove the power supply cables on the transformers.
Figure 9-12 Fiber-optic conductors and power supply cable
3. Release the screwed connections between the phase module and the busbar package
on the rear of the IGCT phase module.
Maintenance
9.7 Repairs
SINAMICS SM150 6SL3845-7NN46-7AA0
174 Operating Instructions 04/2017