EasyManua.ls Logo

Siemens SINAMICS SM150 - Electronics Power Supply

Siemens SINAMICS SM150
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
Open input
An open input is interpreted as "low".
To enable the digital inputs to function, connect terminals MEXT1 and MEXT2. This is done
in one of the following ways:
The incorporated ground reference of the digital inputs
A jumper to terminal M
In this case, the isolation for these digital inputs is removed.
Note
Diagnosis when the 24 VDC auxiliary voltage fuse ruptures
The 24 VDC auxiliary voltage is protected internally by a 4 A fuse. A ruptured fuse is indicated
by loss of the auxiliary power and/or by a diagnostic message. All digital outputs are also
affected by a ruptured fuse. You will not be able to replace this fuse. Replace the component
and send it for repair.
B.2.4.9 Electronics power supply
Table B-22 Power Stack Adapter 2: Electronics power supply
Terminal Designation Technical specifications
1 Electronics ground M Voltage: 24 VDC (18 V to 31.2 V, -25% to +30%)
Power consumption (without DRIVE-CLiQ or digital out‐
puts): 1 A max.
2 N.C.
3 Electronic power supply P24
Max. connectable cross-section: 2.5 mm²
Type: Screw terminal
Technical data and drawings
B.2 Terminal assignments
SINAMICS SM150 6SL3845-7NN46-7AA0
208 Operating Instructions 04/2017

Table of Contents

Other manuals for Siemens SINAMICS SM150