3.5.8 Power Stack Adapter
The Power Stack Adapter (PSA) acts as the physical interface between the power unit and
the open-loop/closed-loop controller. This is where the galvanic isolation (electrical coupling
via light) between the power unit and the open-loop controller takes place. Data is exchanged
between the Power Stack Adapter and the Control Unit via the DRIVE-CLiQ high-speed serial
communication interface.
X11 – X14 Gating of the power semiconductors, inverter phase u
X15, X16, Gating of the power semiconductors, crowbar
X31 – X34 Gating of the the power semiconductors, inverter phase v
X35, X36 Gating of the power semiconductors, braking chopper
X51 – X54 Gating of the power semiconductors, inverter phase w
X241, X242 Selecting Safe Torque Off
X70 – X79 Actual value channels 0 to 9
X81 Trip line
X200 – X202 DRIVE-CLiQ interfaces
X231, X232 Analog and digital outputs
S5.0
S5.1
Switches of the analog inputs, voltage/current measurement AI0
Switches of the analog inputs, voltage/current measurement AI1
X221, X222 Analog and digital inputs, temperature sensor connections
LEDs Diagnostics via LEDs
X210 Electronics power supply
Figure 3-3 Overview of PSA interfaces
Description
3.5 Description of the components
SINAMICS SM150 6SL3845-7NN46-7AA0
38 Operating Instructions 04/2017