3.5.12.2 Measuring socket assignment
The process data acquisition system (PADU8) is used for the diagnosis of analog and digital
converter signals. The process data acquisition system is designed as an optional component.
If the PADU8 is not included, the signals can be read out with the aid of an oscilloscope, for
example, at measuring sockets.
Figure 3-8 Printed circuit board of the diagnostics module
Measuring sockets Signal Measuring sockets Signal
X20/X28 or X29 AO_0 X26/X28 or X29 AO_6
X21/X28 or X29 AO_1 X27/X28 or X29 AO_7
X22/X28 or X29 AO_2 X14/X18 or X19 DO_4
X23/X28 or X29 AO_3 X15/X18 or X19 DO_5
X24/X28 or X29 AO_4 X16/X18 or X19 DO_6
X25/X28 or X29 AO_5 X17/X18 or X19 DO_7
3.5.12.3 Interface description of the connectors
The individual module elements of the DM10 diagnosis module supply several interfaces. The
interfaces are occupied by the following connectors:
X231 PSA connection
X232 PSA connection
X1 PADU8 connection (option G66)
X5 PADU8 connection (option G66)
X31 Closed-loop control interface
X32 Closed-loop control interface
X33 Binary process diagnosis with PADU8 (option G66)
X34 Closed-loop control interface
Description
3.5 Description of the components
SINAMICS SM150 6SL3845-7NN46-7AA0
44 Operating Instructions 04/2017