Version AD586LR
Deviation for ΔT = 25° C 100 μV/mA
Max. change of the output voltage (ΔT)
max
= 70° C 1.75 mV
B.2 Terminal assignments
B.2.1 Control pulpit interface (Terminal Modules TM31 and TM15)
Table B-9 Terminal assignment of customer interface TM15
Terminal module Connec‐
tor
Terminal Internal control
.HC-A11 -X520 3 DI p4022.1 → p840 ON/OFF 1
4 DI p4022.2 → p844 OFF 2
5 DI p4022.3 → p848 OFF 3
6 DI p4022.4 → p2103 Acknowledge faults
7
8 DI p4022.6 → p852 Enable operation
9 DI p4022.7 → p1035 MOP raise
-X521 2 DI p4022.8 → p1036 MOP lower
3 DI p4022.9 → p1020 Fixed speed setpoint bit 0
4 DI p4022.10 → p1021 Fixed speed setpoint bit 1
5 DI p4022.11 → Profibus switchover
6 DI p4022.12 → p1113 Direction reversal
7 DO p4022.13 ← r899.0 Message: Ready for switching on
8 DO p4022.14 ← r899.1 Message: Ready for operation
9 DO p4022.15 ← r899.2 Message: Operation enabled
-X522 2 DO p4022.16 ← r899.3 Message: Fault active
3 DO p4022.17 ← r899.7 Message: Alarm active
4 DO p4022.18 ← r807 Local operation
5 DO p4022.19 ← r2197.3 Drive rotating clockwise
Table B-10 Terminal assignment of customer interface TM31
Terminal module Connec‐
tor
Terminal Internal control
.HC-A11 -X521 1,2 AI p4052.0 → p1070 Main speed setpoint
3,4 AI p4052.1 → p1075 Supplementary speed setpoint
1,2 AO p4071.0 ← r0063 Actual speed value
4,5 AO p4071.1 ← Supplementary actual speed value
Technical data and drawings
B.2 Terminal assignments
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017 201