EasyManua.ls Logo

Siemens SINAMICS SM150 - DM10 Diagnostics Module; Functions

Siemens SINAMICS SM150
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Signal assignment of the interfaces
Connector/pin Signal
X1.3 L
X1.4 Not assigned
X1.5 N
X1.6 Not assigned
X1.7 PE
X2.4 Undervoltage REL_A
X2.5 Undervoltage REL_B
X2.6 Presence of output voltage REL_A
X2.7 Presence of output voltage REL_B
X6.1 / X7.1 / X8.1 / X9.1 PE
X6.2 / X7.2 / X8.2 / X9.2 P-GRD
X6.3 / X7.3 / X8.3 / X9.3 ± 55 V
3.5.12 DM10 diagnostics module
3.5.12.1 Functions
The DM10 diagnosis module performs the following functions:
Monitoring the auxiliary voltages of the internal 1P24 and 1N24 power supply.
Monitoring the external voltage 2P24_1 and the optional external voltage 2P24_2 for
undervoltage.
Monitoring the auxiliary contacts of the 24 V DC miniature circuit-breakers.
Output of eight binary control signals. The logic state of the signal in each case is indicated
by an LED.
Output of eight analog signals to the following signal receivers:
PADU8
Indicating instruments
Control station/I&C
Supply of the digital and analog signals to measuring sockets for simplified diagnosis with
an oscilloscope.
Description
3.5 Description of the components
SINAMICS SM150 6SL3845-7NN46-7AA0
42 Operating Instructions 04/2017

Table of Contents

Other manuals for Siemens SINAMICS SM150

Related product manuals