3.5.6 Circuit-breaker (provided by the customer)
To ensure adequate protection for converters, the circuit-breaker provided by the customer
must fulfill the following requirements:
The maximum time between when the circuit-breaker trips to when a no-current state (I=0)
is reached is 80 ms.
The circuit breaker must be equipped with an undervoltage tripping function.
Avoid additional delay times when controlling the circuit breaker. All commands from the
converter to the circuit breaker must act directly without intervention of coupling relays.
A feedback signal must be available for each of the circuit-breaker states CLOSED and
OPEN. The feedback signals must not be delayed. Consequently, do not use any coupling
relays.
The circuit-breaker is controlled and released from the converter closed-loop control. If this
has not been enabled, under no circumstances should you switch on the circuit-breaker by
external mechanical or electrical means.
To protect the converter transformer, ensure that overcurrent protection is in place.
3.5.7 Converter transformer
A two-winding transformer is required for each Active Line Module. When two complete drive
units are connected in parallel, a three-winding transformer with shifted windings can be used
for suppressing line harmonics.
Consider the following properties during the configuration:
Transformer secondary voltage: 3.3 kV
Minimum leakage inductance: 1 mH
(short-circuit voltage
u
k
=15% to 28% depending on transformer output)
This value includes all the inductance between the line and the converter: Line short-circuit
inductance, transformer inductance, reactor inductance.
Transformer taps for voltage adjustments: 2 x ± 2.5
The winding taps are usually located on the high voltage side of the transformer.
Design the transformer for the following loads:
Max. dU/dt stress at the inverter input terminals: 6 kV/µS
Peak voltage load phase-phase and phase-ground: 8.4 kV
Current load with DC component: approx. 4 A to 5 A
Description
3.5 Description of the components
SINAMICS SM150 6SL3845-7NN46-7AA0
Operating Instructions 04/2017 37