EasyManua.ls Logo

Siemens SINAMICS SM150 - Page 140

Siemens SINAMICS SM150
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Additional setting parameters for analog output 0 (AO0)
Parameter Value Adjustment range
p4077[0] Analog outputs, characteristic value x1 -1000.00 to +1000.00%
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Parameter Value Adjustment range
p4078[0] Analog outputs, characteristic value y1 -20.000 to +20.000 V or mA
Factory setting: 0.000 mA
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used,
the unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Parameter Value Adjustment range
p4079[0] Analog outputs, characteristic value x2 -1000.00 to +1000.00%
Factory setting: 100.00 %
Setting for the x coordinate in % of the second point on the scaling characteristic.
Parameter Value Adjustment range
p4080[0] y2 of the characteristic of the analog out‐
puts
-20.000 to +20.000 V or mA
Factory setting: 20.000 mA
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used,
the unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Additional setting parameters for analog output 1 (AO1)
Parameter Value Adjustment range
p4077[1] Analog outputs, characteristic value x1 -1000.00 to +1000.00%
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Operation
8.4 Functions
SINAMICS SM150 6SL3845-7NN46-7AA0
140 Operating Instructions 04/2017

Table of Contents