3.7 Installation of the TIM 4 as CP in an S7-300
Station control system
122 System Manual, 07/2009, C79000-G8976-C178-07
Standard CPU modules
CPU 312 as of 6ES7 312-1AE13-0AB0
CPU 314 as of 6ES7 314-1AE02-0AB0
(CPU 314 IFM) as of 6ES7 314-5AE02-0AB0
(CPU 315) as of 6ES7 315-1AF01-0AB0
CPU 315-2 DP as of 6ES7 315-2AF01-0AB0
CPU 315F-2 DP as of 6ES7 315-6FF00-0AB0
(CPU 316) as of 6ES7 316-1AG00-0AB0
(CPU 316-2 DP) as of 6ES7 316-2AG00-0AB0
NOTICE
With all CPUs of the type 317, 318 and 319 and with the CPU 315-2 PN/DP, a TIM 4
cannot be operated as a CP in the S7-300 rack. For these CPUs, you require either an
Ethernet TIM (TIM 3V-IE variant, TIM 4R-IE) or a TIM 4 connected to the CPU as a
standalone TIM over its MPI interface.
Compact CPU modules
CPU 312C as of 6ES7 312-5BE03-0AB0
CPU 313C as of 6ES7 313-5BE00-0AB0
CPU 313C-2PtP as of 6ES7 313-6BE00-0AB0
CPU 313C-2DP as of 6ES7 313-6CE00-0AB0
CPU 314C-2PtP as of 6ES7 314-6BF00-0AB0
CPU 314C-2DP as of 6ES7 314-6CF00-0AB0
Instead of an S7-300 standard or compact CPU, one of the following C7 control systems
may also be used.
C7 control systems
(C7-623/P) as of 6ES7 623-1DE00-0AE3
(C7-626/P) as of 6ES7 626-1DG02-0AB3
(C7-626/P DP) as of 6ES7 626-2DG02-0AB3
(C7-633/P) as of 6ES7 633-1DF00-0AB3
(C7-633/DP) as of 6ES7 633-2BF00-0AB3
(C7-634/P) as of 6ES7 634-1DF00-0AB3
(C7-634/DP) as of 6ES7 634-2BF00-0AB3
C7-635 Key as of 6ES7 635-2EC00-0AB3
C7-635 Touch as of 6ES7 635-2EB00-0AB3
C7-636 Key as of 6ES7 636-2EC00-0AB3
C7-636 Touch as of 6ES7 636-2EB00-0AB3