Introduction to the SINAUT ST7 system
1.3 SINAUT TIM communication modules
Station control system
24 System Manual, 07/2009, C79000-G8976-C178-07
● Can be operated without a fan
● A backup battery and a memory module (C-PLUG) can be installed as options.
The following figure shows the ports of the TIM 4R-IE (schematic representation with front
panel removed).
24 V
2 x
RS-232/RS-485 port
(9-pin, male):
Access to WAN over
External Modem
2 x
RJ-45 port
Access to Ethernet
Figure 1-4 Ports of the TIM 4R-IE
1.3.7 Technical specifications of the TIM 4R-IE
Technical specifications of the TIM 4R-IE
TIM 4R-IE
General
Transmission rate
• RS-232/RS-485
• Ethernet
• 50 to 38,400 bps
• 10/100 Mbps autosensing
Interfaces
• Communication port,
electrical
• Connection to power supply
• Slot for exchangeable media
• - 9-pin D-sub male, RS-232,
can be switched over to RS-485;
- RJ-45 (10/100 Mbps; TP)
• 1 x 2-pin plug-in terminal strip
• C-PLUG (optional)
Cable length
• RS-232
• RS-485
• RJ-45
• max. 6 m
• max. 30 m
• max. 10 m
Power supply 24 V DC; min. 20.4 V; max. 28.8 V