Installing and putting a TIM into operation
4.7 Startup activities of the TIM module
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
175
4.7.2 Startup activities of the TIM 4R-IE
Introduction
During startup, the LEDs on the front panel of the TIM 4R-IE have a different significance
than during normal operation. They are optical indicators of the various startup phases and
provide detailed information about any errors detected during startup. During startup on the
TIM 4R-IE, the "BATF", "P1" and "P2" LEDs have no significance.
LED displays during startup
The following table summarizes the startup phases.
Table 4- 23 LED activity on the TIM 4R-IE during the various startup phases
Phase Activity SF RUN STOP KBUS TXD1 RXD1 TXD2 RXD2
1 Power ON, followed by hardware
initialization
On On On On On On On On
2 Loading the operating system from
flash memory
Off On On On On On On On
3 Starting VxWorks operating
system
Off Off On On On On On On
4 Loading and starting TIM firmware Off Off Off On On On On On
5 Initializing flash file system and
starting the start manager
Off Flashe
s
On Off Off Off Off Off
6 Loading and starting P bus driver Off Flashe
s
On On Off Off Off Off
7 Loading and starting subscriber
management (SubA)
Off Flashe
s
On Off On Off Off Off
8 Loading and starting LAN-COM Off Flashe
s
On On On Off Off Off
9 Loading and starting subscriber
management (MesA)
Off Flashe
s
On Off Off On Off Off
10 Loading and starting time-of-day
driver
Off Flashe
s
On On Off On Off Off
11 Loading and starting the TD7
software of the TIM (TD7onTIM)
on the TIM
Off Flashe
s
On Off On On Off Off
12 Loading and starting WAN driver Off Flashe
s
On On On On Off Off
13 Startup completed or aborted
13a Startup completed without error Off On Off X
1)
X
1)
X
1)
X
1)
X
1)
13b Startup completed with error On Off On X
2)
X
2)
X
2)
X
2)
X
2)
13c Startup aborted - user parameter
assignment missing Module
expects parameter SDBs
Off Off On On Flashes On Flashes On
13d Startup aborted - No firmware
loaded.
Off Off On Flashes On Flashes On Flashes