Installing and putting a TIM into operation
4.5 Installing a TIM
Station control system
System Manual, 07/2009, C79000-G8976-C178-07
165
Permitted ambient temperature
The SINAUT ST7 components can be operated in the same temperature range specified for
the S7-300.
Table 4- 20 Permitted ambient temperatures for the SINAUT TIM modules
Installation position Permitted ambient temperature (operation)
TIM
Horizontally installed rack
0 to 60 °C
TIM
Vertically installed rack
0 to 40 °C
Dimensions for installing the SINAUT TIM modules
Table 4- 21 Dimensions for installing the SINAUT TIM modules
Module Module width Module height Max. depth
Communications module
TIM 3V-IE and
TIM 3V-IE Advanced
40 mm 125 mm 120 mm or 150 mm with
open front panel
Communications module
TIM 4 and TIM 4R-IE
80 mm 125 mm 120 mm or 180 mm with
open front panel
4.5.6 Connecting the TIM to the power supply
WARNING
Connecting the TIM module to a live power supply can damage the module. Connect the
module to the power supply only when the power supply is off.