EasyManua.ls Logo

Siemens SINAUT ST7 - Technical Specifications of the LTOP Overvoltage Protection Module

Siemens SINAUT ST7
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Introduction to the SINAUT ST7 system
1.6 LTOP overvoltage protection modules
Station control system
48 System Manual, 07/2009, C79000-G8976-C178-07
Figure 1-14 LTOP2 overvoltage protection module
The LTOP overvoltage protection module is available in two variants:
LTOP 1
Overvoltage protection module for use at the start or end of a 2-wire dedicated line.
LTOP2
Overvoltage protection module for use at the start or end of a 4-wire dedicated line or in a 2-
wire tapping point. In a 4-wire tapping point, two LTOP2 modules are required.
Table 1- 3 Overview of the LTOP modules
Short name Order no. Explanation
LTOP1 6NH9821-0BC11 Single line transformer LTOP1, with one OPM
overvoltage protection module for use at the start or
end of a 2-wire dedicated line
LTOP2 6NH9821-0BC12 Double line Transformer LTOP2, with two OPM
overvoltage protection modules for use at the start or
end of a 4-wire dedicated line or a 2-wire tapping
point
OPM 6NH9821-0BB00 OPM overvoltage protection module for LTOP1 and
LTOP2, plug-in (pack of 4)
The two LTOP variants have both screw terminals and an RJ-12 Western jack. The WAN
cable (RJ-12 - RJ-12) supplied with the MD2 and MD3 modems (used as dedicated line
modems) can be connected directly to this RJ-12 jack.
Note
The LTOP modules are not suitable for protecting dial-up connections (telephone and ISDN
network). Companies such as Phoenix and Dehn offer TAE6, S0, RJ-12, and RJ-45 jacks
with overvoltage protection.
1.6.2 Technical specifications of the LTOP overvoltage protection module
LTOP
Transmission paths Private transmission lines with or without loading coils
Transmission ratio 1 : 1; ± 5 % (e.g. 600/600 ohms in the voice band)

Table of Contents

Other manuals for Siemens SINAUT ST7

Related product manuals